MIL-THERM 145
You are here Homepage / Services / Cables & Wires / Single wires / MIL-THERM 145

MIL-THERM 145*** - single core -55 to 145 °C
Application area
Used in the wiring technology of control cabinets, switchgear, lights, electrical heaters and electrical machines with increased temperature load. Furthermore, the core is used in traffic engineering (motor vehicles, commercial vehicles, buses, ships, railroads and aircraft). These cores are characterized by excellent processing safety and good oil resistance. The core insulation does not retract during soldering.
Structure
Conductor made of tinned copper wires according to DIN VDE 0295 class 5 (IEC 228, class 5). Insulation made of polyolefin - copolymer with extended temperature range and at the same time improved behavior in case of fire.
DNV, VDE, GL Approved
Operating voltage Operating temperature Test voltage | up to 0,75mm² 450/750V from 1,00mm² 600/1000V -55 to +145°C (Fixed) -35 to +120°C (Free moving) 3.500V 4 × D |
---|
Item no. | mm² (wires) | Ø mm | Weight approx. kg/km | Cu number kg/km |
---|---|---|---|---|
MIL-THERM145025.X MIL-THERM145050.X MIL-THERM145075.X MIL-THERM145100.X MIL-THERM145150.X MIL-THERM145250.X MIL-THERM145400.X MIL-THERM145600.X MIL-THERM145910.X MIL-THERM145916.X MIL-THERM145925.X MIL-THERM145935.X MIL-THERM145950.X MIL-THERM145970.X MIL-THERM145995.X MIL-THERM145820.X | 0,25(19) 0,50(19) 0,75(24) 1,00(32) 1,50(30) 2,50(50) 4,0(56) 6,0(84) 10(80) 16(126) 25(196) 35(276) 50(396) 70(361) 95(475) 120(608) | 1,5 1,8 2,2 2,5 3,1 3,6 4,3 5,4 6,7 8,3 10,0 11,4 13,5 15,7 18,1 20,1 | 5 9 13 15 22 34 47 72 120 190 290 400 550 770 1010 1270 | 2,4 4,8 7,2 9,6 14,4 24,0 38,4 57,6 96,0 154 240 336 480 672 912 1152 |
X = Main color code